SP2 Sao Paulo - Network Interconnection Specifications


Equinix SP2 IBX Data Center

Al. Araguaia 3641
Tamboré Barueri, SP CEP: 06455-000

Contact Sales:

Tech Specs

Power
  • Electrical Capacity – Average of 4 kW, maximum of 12 kW, total of 12 MW of power available
  • UPS Configuration – 2 x (2 x 825 kVA (742.5 kW)) in 2N configuration - 1st phase # of Utility Feeders – Two lines (N+1) - 34.5 kV
  • Utility Voltage – 34.5 kV
  • Standby Power Config. – 2 x [2,800 KVA (4 x 700 kVA)] in N+1 configuration
  • Lighting – Fluorescent lamps (4x 14 W)
Cooling
  • Cooling Capacity – 4.0 kVa per cabinet (13,648 BTUH)
  • Cooling Plant – CRAC equipment in N+1 configuration; ambient temperature within technical areas maintained at 22 ± 2°C
Security
  • Physical – Doors (like sluice), in the building reception; security doors between reception and the production environment, which allows the passage of only one visitor at a time
  • Human – Guardhouse with 24x7x365 monitoring
  • Electronic – 24x7x365 CCTV recordings with motion detectors, card readers, biometric handscan reader plus PIN code security to servers area, perimeter security.
Interconnection
  • System – Patch-pannel core
  • Cross Connects – CAT5, CAT6A, and Fiber
  • Equinix Metro Connect – Metro Connects to SP1 IBX, RJ1 IBX and RJ2 IBX
  • Equinix Internet Exchange™ – PTTMetro-SP IXP

Awards & Accreditations

Equinix is committed to providing standards-compliant data centers, with many of our facilities having undergone audits for SSAE16 or receiving certification for ISO or LEED. Additionally, our IBX data centers are the recipients of industry awards in a variety of categories including operational reliability, market leadership and green initiatives. Please contact us to learn more about a particular facility.